Skip to content
Fault guide · GivEnergy EPS / backup

GivEnergy EPS Not Working During a Power Cut

You have a GivEnergy battery but the house went dark during a grid outage. EPS (Emergency Power Supply) is disabled by default on GivEnergy's hybrid inverters and the AC 3.0, and requires both a software setting and a dedicated wired circuit. This guide covers every reason EPS may have failed — and how to set it up correctly. For the general technical background, see how backup power works.
Free remote diagnostic £125 only if we fix it remotely
  • EPS disabled by default — must be enabled in portal
  • Requires dedicated wired circuit — not whole house
  • SoC, overload, and wiring causes covered
EPS configuration is model-specific

EPS setup on GivEnergy varies between Gen 1, Gen 2 and Gen 3 hybrids (the All-in-One backs up through a Giv-Gateway instead). Whether your system has a wired EPS circuit, what the SoC minimum should be set to, and which portal settings apply — we can review and configure this remotely.

Book your free remote diagnosticGivEnergy hub

Not affiliated with GivEnergy Ltd. Independent diagnosis and configuration.

Absolutely wonderful. Would recommend without hesitation. I had an issue I was thinking would never be fixed and they fixed it. Help, advice and support every step of the way. I can't recommend highly enough. Thank you so much ⭐

jill brocklehurst · Jul 2026 Google

I have a GivEnergy system consisting of two batteries, two inverters and a controlling EMS (Energy Management System) which has not worked since Nov 2025. After six months I discovered Solar Tech Support, reached out to them and Ron phoned me back – how often do you get that service? Could not be more helpful – worked directly with me over the phone, outside what I would call normal working hours. Lucid explanations and we were able to discuss the issues and history using camera and email history. As this was a very rare setup, Ron was able to access an EMS expert in the field to confirm the solution. One sunny day in, I am now only paying for standing charge and a few pence for spikes in grid consumption while battery catches up with house demand.

Ian · May 2026 Trustpilot

Prompt and useful support regarding my Sunsynk system lack of performance. Ronald simplified the technical issues to make them understandable. Many thanks, looking forward to follow up.

Patrick Keenan · May 2026 Trustpilot

Unfortunately, only weeks after Givenergy went into receivership, our system failed. Our installers were unhelpful in the extreme but Solar Tech Support were able to diagnose a terminal problem with our Gen 1 AC3 inverter. They advised regarding the available options and (having decided to buy a replacement Givenergy inverter as the simplest solution) they were able to get us up and running. They made themselves readily available to talk through the process and manage any faults. I would have no problem recommending them.

Stephen Paul · Aug 2026 Google

Made contact for assistance with my GiveEnergy battery that wasn't discharging. Ronald looked at my issue the same day, identified the root cause with a clear explanation of what was going on along with some options on how to remediate the issue. So far my battery is now working and keeping my fingers crossed that it stays this way. Ronald is a very experienced and knowledgeable engineer and I would recommend.

Al · Jul 2026 Google

I contacted Solar Tech Support because I had a problem with my legacy GiveEnergy installation. within 24 hours they had diagnosed the problem and offered advice on resolution. Because they were unable to fix the problem there was no charge! This despite numerous time consuming emails. I am currently trying to engage with the original installer but if that is unsuccessful I will go back to Solar Tech Support and ask them to repair the system with a retrofit. Very knowledgeable and responsive. I highly recommend them.

Tim Hatt · Aug 2026 Google
Understanding EPS

What GivEnergy EPS actually does — and what it doesn't

EPS (Emergency Power Supply) is GivEnergy's battery backup function. Understanding exactly how it works is essential before diagnosing why it failed.

WHAT EPS DOES

Powers a dedicated backup circuit

When the grid fails, GivEnergy's EPS mode switches the dedicated EPS output terminals from grid power to battery power. On a hybrid or AC-coupled inverter that changeover takes about a second in our experience, so it is a quick restart rather than an uninterrupted handover. A Giv-Gateway on an All-in-One is quicker: we see about 20 ms. Only circuits wired to those specific terminals receive backup power.

WHAT EPS DOESN'T DO

Does not back up the whole house

The main consumer unit and all sockets and lights not wired to the EPS circuit remain off during a grid outage. EPS is for essential circuits only — typically a few key sockets, boiler, or lights selected at installation.

WHAT EPS NEEDS

Both wiring and settings

EPS requires: (1) a dedicated EPS output circuit physically wired by the installer to the inverter's backup terminals, AND (2) EPS mode enabled in the GivEnergy portal. Missing either one means no backup power.

Not all GivEnergy installations include EPS wiring. Many UK installers do not wire the EPS output circuit as standard — it is an optional additional cost. If you were not told at installation that EPS backup was included, your system may not have a wired EPS circuit at all. This is the most important thing to establish before adjusting any settings.
Cause 1 — most common
Most common

EPS mode is not enabled in the portal

EPS is disabled by default on every GivEnergy hybrid inverter and on the AC 3.0. It must be explicitly enabled in the GivEnergy portal. This is the most common reason backup power doesn't work — the physical wiring is correct but the inverter has never been told to use it.

How to check if EPS is enabled

1
Log into the GivEnergy portal

Go to givenergy.cloud → My Inverter → System Mode Settings.

2
Look for the EPS / backup power setting

EPS settings are typically found in the System Mode Settings or Advanced Settings section depending on your portal version. Look for a toggle or option labelled EPS, Emergency Power Supply, or Backup. If it is set to Off or Disabled, this is your problem.

Note: The exact location of the EPS setting varies between portal versions and inverter generations. On some models it is under Battery Options rather than System Mode Settings. If you cannot find it, see the how to enable EPS section below, or book a remote session for model-specific guidance.
3
Check if EPS was reset by a firmware update

GivEnergy firmware updates can reset settings including EPS mode back to defaults. If EPS was working and then stopped after an update, check whether the setting has reverted to disabled.

Cause 2 — very common
Wiring — requires engineer

No dedicated EPS output circuit was installed

Even if EPS mode is enabled in the portal, backup power only reaches circuits that are physically wired to the inverter's EPS output terminals. Many UK GivEnergy installations do not include this wiring — it is an optional additional cost that many installers don't include as standard.

How to tell if you have an EPS circuit

→Check your original installation quote or contract — does it mention EPS wiring, backup circuit, or emergency supply as a line item?
→Look at your consumer unit — is there a separate MCB or circuit labelled EPS, Backup, or Emergency?
→Check the inverter itself — are there cables connected to the backup/EPS output terminals? (Visual check of the terminal block labels only — do not open the inverter)
→Ask your original installer whether EPS output wiring was included in the installation

Adding an EPS circuit — what's involved

Adding an EPS circuit is an electrical installation job. A qualified electrician or GivEnergy-experienced engineer runs a dedicated circuit from the inverter's EPS output terminals to a sub-board or specific sockets and circuits that you want backed up.

You need to decide which loads to back up — common choices are a key socket, the boiler, fridge, and critical lighting. The total load must not exceed the inverter's EPS output rating: 2.6kW on a Gen 1 hybrid, 3.6kW on a Gen 2 or Gen 3 3.6/5.0kW hybrid, 8 to 10kW on a Gen 3 8.0/10.0kW hybrid and 3kW on the AC 3.0. The Gen 1 All-in-One (6kW and 3.6kW models) has no EPS terminals: it backs up the whole house through a Giv-Gateway (6kW continuous), or not at all.

This is a notifiable electrical installation and should be done by a Part P registered electrician or a qualified solar engineer.

Do not attempt EPS wiring yourself. The inverter's EPS output terminals are live electrical connections. This wiring must be done by a qualified engineer. Incorrect wiring could backfeed mains voltage onto a circuit assumed to be dead during an outage — a serious safety risk for engineers working on the grid.
Cause 3
Battery SoC

Battery was below the minimum SoC reserve at the time of the outage

GivEnergy EPS will not activate if the battery state of charge is at or below the EPS reserve threshold. If the outage happened at night after a long discharge period, or the battery has been undercharging due to a separate fault, EPS may have had nothing to draw from.

Check battery SoC at time of outage

In the GivEnergy portal, navigate to the battery SoC graph and look at what the SoC reading was at the time the outage occurred. If the battery was at or near the reserve minimum (or at 0%), EPS had insufficient charge to operate.

The EPS reserve setting is typically in Battery Options under the minimum SoC or reserve percentage. Check what this is set to — if the battery was above this at the time of the outage but EPS still didn't work, the SoC is not the cause.

Configuring the EPS reserve correctly

The EPS reserve (minimum SoC) determines how much battery charge is held back specifically for backup power. Setting it too low means EPS may be unavailable when you need it. Setting it too high means less battery capacity for daily use.

→A 20% reserve provides approximately 1–2 hours of moderate EPS load on a 5kWh battery
→Set the reserve based on how long you want backup capability — not so high it impacts daily operation
→Consider keeping Timed Charge active overnight so the battery enters each night with a full charge ahead of potential outages
Cause 4
Overload

EPS tripped immediately — load exceeded inverter backup rating

EPS activated but then cut out within seconds. The total power draw on the EPS circuit exceeded the inverter's backup power rating, triggering the overload protection. This produces the fault code STORAGE_ERROR_BACKUP_OVERLOAD_FAULT.

GivEnergy backup power ratings

Backup output ratings
Gen 1 hybrid (3.6/5.0 kW)2.6kW
Gen 2 hybrid3.6kW
Gen 3 hybrid (3.6/5.0 kW)3.6kW
Gen 3 hybrid (8.0/10.0 kW)8–10kW
Gen 1 All-in-One (whole house, via Giv-Gateway)6kW
AC 3.0 (AC-coupled)3kW

The Gen 1 figure is the most it can supply from the battery alone. Ratings vary by inverter model. Always verify against your specific model's datasheet before sizing an EPS circuit.

What to do about an overload

STORAGE_ERROR_BACKUP_OVERLOAD_FAULTCheck the portal event log for this code — if present, the load on the EPS circuit exceeded the inverter's backup power rating.
Review what loads are wired to the EPS circuit — add up their total wattage at startup (startup draw is often higher than running draw).
Remove high-draw appliances from the EPS circuit — electric showers, kettles, and electric ovens are not suitable EPS loads.
Any EPS circuit wiring changes require a qualified engineer.

Suitable and unsuitable EPS loads

Suitable EPS loads
✓Gas boiler (control board only, typically 100–200W)
✓Fridge / freezer (100–200W running, brief higher startup)
✓LED lighting (10–20W per circuit)
✓Phone/device chargers (20–100W)
✓Router and broadband equipment (10–30W)
✓Low-draw medical equipment (always check with manufacturer)
Unsuitable EPS loads
✗Electric shower (7–10kW — far exceeds any EPS rating)
✗Electric cooker or hob (3–12kW)
✗Kettle (2–3kW — brief but trips overload)
✗Tumble dryer (2–3kW)
✗Immersion heater (2–3kW)
✗Air conditioning units (1–5kW with high startup draw)

Total load on the EPS circuit must not exceed the inverter backup rating. Account for startup surges — motor-driven loads like fridges draw 2–3× their running wattage for 1–2 seconds on startup.

Configuration
How to enable EPS

Enabling and configuring GivEnergy EPS correctly

Before enabling EPS in the portal, confirm that a dedicated EPS output circuit was physically wired at installation. Enabling EPS without the correct wiring has no effect — it will not provide backup power and may cause unexpected behaviour.

EPS setup checklist

1
Confirm EPS wiring exists

Verify with your installer documentation or by visually checking the consumer unit for a dedicated EPS/backup circuit. If not installed, contact a qualified engineer to add one before proceeding.

2
Enable EPS in the GivEnergy portal

Go to givenergy.cloud → My Inverter → System Mode Settings. Find the EPS or backup power setting and enable it. Press Submit to apply. The exact label and location varies between portal versions — it may be under Battery Options or Advanced Settings on some models.

Remote configuration: EPS settings can be updated remotely via the portal. No site visit is needed just to enable or reconfigure the EPS setting — only if wiring changes are required.
3
Set the EPS reserve (minimum SoC)

Under Battery Options, set the minimum SoC reserve to the level that gives you your desired backup duration. A 20–30% reserve is a reasonable starting point for most households. This is the charge held back exclusively for EPS use.

4
Have EPS tested

Do not simulate a power cut yourself. A competent person tests EPS by isolating the supply upstream of the inverter, with instruments on. They check that the backed-up circuits stay powered, then that the system reconnects to the grid on its own.

Safety: EPS testing involves working near live electrical equipment, so it is an engineer job. We can check the EPS settings remotely before the test.
Also check

Appliance compatibility with EPS

Some appliances are sensitive to the changeover gap when EPS activates. On hybrid and AC-coupled EPS terminals the handover takes about a second in our experience, so computers, NAS devices and some boiler controls will restart during the switchover even when EPS is working correctly. This is not an EPS fault — it's a limitation of the technology. A UPS (uninterruptible power supply) on sensitive equipment can bridge this gap.

Also check

EPS and the inverter status light

During EPS operation, the inverter status light behaviour changes — the inverter is no longer connected to the grid and operates in island mode. This is normal. If the battery depletes fully during EPS and the grid is still down, all power will be cut. The inverter will restart automatically when grid power returns.

This is a brand-specific version of our general no backup during power cut guide, which covers all brands.

FAQ

GivEnergy EPS questions

No. GivEnergy EPS only powers circuits physically wired to the inverter's dedicated EPS output terminals. Your main consumer unit and all sockets and lights not on the EPS circuit will remain off. EPS is designed for essential loads only — a few key circuits selected at installation time. If you want whole-house backup, that requires a different system architecture. The Gen 1 All-in-One (6kW and 3.6kW models) has no EPS: with a Giv-Gateway it backs up the whole house, without one it has no backup.
Duration depends on the battery capacity, the SoC at the start of the outage, the EPS reserve setting, and the load on the backup circuit. As a rough guide: a 5kWh battery at 80% charge running a 200W load would last approximately 20 hours. Running a 1kW load (fridge + a few lights + boiler) would last around 4 hours from that starting point. Reduce load to extend duration.
Yes, in most cases. A GivEnergy-experienced electrician can add the EPS output circuit retrospectively. The inverter already has the backup terminals — it's a matter of wiring the correct circuits to them and enabling EPS in the portal. This is a notifiable electrical installation and must be done by a qualified Part P registered electrician.
Two possible causes: the boiler isn't wired to the EPS circuit (it's on a standard circuit that goes off during an outage), or the boiler control system is sensitive to the EPS changeover gap and resets. On hybrid and AC-coupled EPS terminals that changeover takes about a second in our experience, which is long enough to drop most boiler controls. Some need to complete a power-on sequence and won't do so correctly after the interruption. A small UPS on the boiler bridges the gap if that is the issue.
Yes. EPS draws from the battery regardless of whether solar panels are generating. During a night-time power cut, EPS will run entirely from stored battery charge. In a daytime cut, a GivEnergy hybrid inverter also charges the battery from the panels while they are generating. An AC 3.0 does not charge from solar during a power cut.
No. The AC 3.0 only runs the battery. Your panels go through a separate solar inverter, and that inverter switches off when the grid fails, as it is required to. So in a power cut an AC 3.0 runs the EPS circuit from the battery until it runs down, and it does not recharge from solar until the grid is back. A GivEnergy hybrid inverter is different: the panels feed it directly, so it keeps charging the battery while they are generating. A GivEnergy All-in-One with a Giv-Gateway also keeps charging from solar in a power cut, with the Gateway backing up the whole house.
Book

EPS not working? We'll find out why and configure it correctly.

Tell us whether you had EPS wiring at installation, what the battery was showing at the time of the outage, and what the portal settings look like. We'll identify the cause and configure EPS correctly for your system.

  • Not affiliated with GivEnergy Ltd
  • Remote fix: £125, only if we fix it; first-time EPS setup in the portal is a fixed £145
  • EPS settings changes done remotely — no site visit needed for configuration

By submitting you agree to be contacted about your diagnostic request. We don't share your data with 3rd parties.

Call 07944 877 329 Book free diagnostic