Absolutely wonderful. Would recommend without hesitation. I had an issue I was thinking would never be fixed and they fixed it. Help, advice and support every step of the way. I can't recommend highly enough. Thank you so much ⭐
GivEnergy EPS Not Working During a Power Cut
- EPS disabled by default — must be enabled in portal
- Requires dedicated wired circuit — not whole house
- SoC, overload, and wiring causes covered
EPS setup on GivEnergy varies between Gen 1, Gen 2 and Gen 3 hybrids (the All-in-One backs up through a Giv-Gateway instead). Whether your system has a wired EPS circuit, what the SoC minimum should be set to, and which portal settings apply — we can review and configure this remotely.
Book your free remote diagnosticGivEnergy hubNot affiliated with GivEnergy Ltd. Independent diagnosis and configuration.
I have a GivEnergy system consisting of two batteries, two inverters and a controlling EMS (Energy Management System) which has not worked since Nov 2025. After six months I discovered Solar Tech Support, reached out to them and Ron phoned me back – how often do you get that service? Could not be more helpful – worked directly with me over the phone, outside what I would call normal working hours. Lucid explanations and we were able to discuss the issues and history using camera and email history. As this was a very rare setup, Ron was able to access an EMS expert in the field to confirm the solution. One sunny day in, I am now only paying for standing charge and a few pence for spikes in grid consumption while battery catches up with house demand.
Prompt and useful support regarding my Sunsynk system lack of performance. Ronald simplified the technical issues to make them understandable. Many thanks, looking forward to follow up.
Unfortunately, only weeks after Givenergy went into receivership, our system failed. Our installers were unhelpful in the extreme but Solar Tech Support were able to diagnose a terminal problem with our Gen 1 AC3 inverter. They advised regarding the available options and (having decided to buy a replacement Givenergy inverter as the simplest solution) they were able to get us up and running. They made themselves readily available to talk through the process and manage any faults. I would have no problem recommending them.
Made contact for assistance with my GiveEnergy battery that wasn't discharging. Ronald looked at my issue the same day, identified the root cause with a clear explanation of what was going on along with some options on how to remediate the issue. So far my battery is now working and keeping my fingers crossed that it stays this way. Ronald is a very experienced and knowledgeable engineer and I would recommend.
I contacted Solar Tech Support because I had a problem with my legacy GiveEnergy installation. within 24 hours they had diagnosed the problem and offered advice on resolution. Because they were unable to fix the problem there was no charge! This despite numerous time consuming emails. I am currently trying to engage with the original installer but if that is unsuccessful I will go back to Solar Tech Support and ask them to repair the system with a retrofit. Very knowledgeable and responsive. I highly recommend them.
What GivEnergy EPS actually does — and what it doesn't
EPS (Emergency Power Supply) is GivEnergy's battery backup function. Understanding exactly how it works is essential before diagnosing why it failed.
Powers a dedicated backup circuit
When the grid fails, GivEnergy's EPS mode switches the dedicated EPS output terminals from grid power to battery power. On a hybrid or AC-coupled inverter that changeover takes about a second in our experience, so it is a quick restart rather than an uninterrupted handover. A Giv-Gateway on an All-in-One is quicker: we see about 20 ms. Only circuits wired to those specific terminals receive backup power.
Does not back up the whole house
The main consumer unit and all sockets and lights not wired to the EPS circuit remain off during a grid outage. EPS is for essential circuits only — typically a few key sockets, boiler, or lights selected at installation.
Both wiring and settings
EPS requires: (1) a dedicated EPS output circuit physically wired by the installer to the inverter's backup terminals, AND (2) EPS mode enabled in the GivEnergy portal. Missing either one means no backup power.
EPS mode is not enabled in the portal
EPS is disabled by default on every GivEnergy hybrid inverter and on the AC 3.0. It must be explicitly enabled in the GivEnergy portal. This is the most common reason backup power doesn't work — the physical wiring is correct but the inverter has never been told to use it.
How to check if EPS is enabled
Go to givenergy.cloud → My Inverter → System Mode Settings.
EPS settings are typically found in the System Mode Settings or Advanced Settings section depending on your portal version. Look for a toggle or option labelled EPS, Emergency Power Supply, or Backup. If it is set to Off or Disabled, this is your problem.
GivEnergy firmware updates can reset settings including EPS mode back to defaults. If EPS was working and then stopped after an update, check whether the setting has reverted to disabled.
No dedicated EPS output circuit was installed
Even if EPS mode is enabled in the portal, backup power only reaches circuits that are physically wired to the inverter's EPS output terminals. Many UK GivEnergy installations do not include this wiring — it is an optional additional cost that many installers don't include as standard.
How to tell if you have an EPS circuit
Adding an EPS circuit — what's involved
Adding an EPS circuit is an electrical installation job. A qualified electrician or GivEnergy-experienced engineer runs a dedicated circuit from the inverter's EPS output terminals to a sub-board or specific sockets and circuits that you want backed up.
You need to decide which loads to back up — common choices are a key socket, the boiler, fridge, and critical lighting. The total load must not exceed the inverter's EPS output rating: 2.6kW on a Gen 1 hybrid, 3.6kW on a Gen 2 or Gen 3 3.6/5.0kW hybrid, 8 to 10kW on a Gen 3 8.0/10.0kW hybrid and 3kW on the AC 3.0. The Gen 1 All-in-One (6kW and 3.6kW models) has no EPS terminals: it backs up the whole house through a Giv-Gateway (6kW continuous), or not at all.
This is a notifiable electrical installation and should be done by a Part P registered electrician or a qualified solar engineer.
Battery was below the minimum SoC reserve at the time of the outage
GivEnergy EPS will not activate if the battery state of charge is at or below the EPS reserve threshold. If the outage happened at night after a long discharge period, or the battery has been undercharging due to a separate fault, EPS may have had nothing to draw from.
Check battery SoC at time of outage
In the GivEnergy portal, navigate to the battery SoC graph and look at what the SoC reading was at the time the outage occurred. If the battery was at or near the reserve minimum (or at 0%), EPS had insufficient charge to operate.
The EPS reserve setting is typically in Battery Options under the minimum SoC or reserve percentage. Check what this is set to — if the battery was above this at the time of the outage but EPS still didn't work, the SoC is not the cause.
Configuring the EPS reserve correctly
The EPS reserve (minimum SoC) determines how much battery charge is held back specifically for backup power. Setting it too low means EPS may be unavailable when you need it. Setting it too high means less battery capacity for daily use.
EPS tripped immediately — load exceeded inverter backup rating
EPS activated but then cut out within seconds. The total power draw on the EPS circuit exceeded the inverter's backup power rating, triggering the overload protection. This produces the fault code STORAGE_ERROR_BACKUP_OVERLOAD_FAULT.
GivEnergy backup power ratings
The Gen 1 figure is the most it can supply from the battery alone. Ratings vary by inverter model. Always verify against your specific model's datasheet before sizing an EPS circuit.
What to do about an overload
STORAGE_ERROR_BACKUP_OVERLOAD_FAULTCheck the portal event log for this code — if present, the load on the EPS circuit exceeded the inverter's backup power rating.Suitable and unsuitable EPS loads
Total load on the EPS circuit must not exceed the inverter backup rating. Account for startup surges — motor-driven loads like fridges draw 2–3× their running wattage for 1–2 seconds on startup.
Enabling and configuring GivEnergy EPS correctly
Before enabling EPS in the portal, confirm that a dedicated EPS output circuit was physically wired at installation. Enabling EPS without the correct wiring has no effect — it will not provide backup power and may cause unexpected behaviour.
EPS setup checklist
Verify with your installer documentation or by visually checking the consumer unit for a dedicated EPS/backup circuit. If not installed, contact a qualified engineer to add one before proceeding.
Go to givenergy.cloud → My Inverter → System Mode Settings. Find the EPS or backup power setting and enable it. Press Submit to apply. The exact label and location varies between portal versions — it may be under Battery Options or Advanced Settings on some models.
Under Battery Options, set the minimum SoC reserve to the level that gives you your desired backup duration. A 20–30% reserve is a reasonable starting point for most households. This is the charge held back exclusively for EPS use.
Do not simulate a power cut yourself. A competent person tests EPS by isolating the supply upstream of the inverter, with instruments on. They check that the backed-up circuits stay powered, then that the system reconnects to the grid on its own.
Appliance compatibility with EPS
Some appliances are sensitive to the changeover gap when EPS activates. On hybrid and AC-coupled EPS terminals the handover takes about a second in our experience, so computers, NAS devices and some boiler controls will restart during the switchover even when EPS is working correctly. This is not an EPS fault — it's a limitation of the technology. A UPS (uninterruptible power supply) on sensitive equipment can bridge this gap.
EPS and the inverter status light
During EPS operation, the inverter status light behaviour changes — the inverter is no longer connected to the grid and operates in island mode. This is normal. If the battery depletes fully during EPS and the grid is still down, all power will be cut. The inverter will restart automatically when grid power returns.
Battery not charging overnight — low SoC means less EPS reserve too.
See battery not charging →Battery fault codes including EPS overload and protection events.
See red light / battery alarm →Firmware updates that reset EPS mode or other system settings.
See firmware issues →Browse all GivEnergy fault guides — battery, portal, BMS comms, firmware and more.
See all GivEnergy problems →This is a brand-specific version of our general no backup during power cut guide, which covers all brands.
GivEnergy EPS questions
EPS not working? We'll find out why and configure it correctly.
Tell us whether you had EPS wiring at installation, what the battery was showing at the time of the outage, and what the portal settings look like. We'll identify the cause and configure EPS correctly for your system.
- Not affiliated with GivEnergy Ltd
- Remote fix: £125, only if we fix it; first-time EPS setup in the portal is a fixed £145
- EPS settings changes done remotely — no site visit needed for configuration
GivEnergy problems? Remote fixes: no fix, no fee.
I’ve worked on hundreds of GivEnergy systems and know the kit inside out. If yours is playing up, my promise is simple — no fix, no fee: just £125 if we fix it, free if we don’t.
We use cookies to measure traffic and ads, sharing limited hashed data with Meta and Google. Decline keeps only essential cookies. Privacy policy
Got a solar fault or need a quick answer? Drop us a message and we usually reply within a few minutes. Mon–Fri, 9am–7pm.